BYF-63 RCD 10KA Type B AC+A+Smoothing DC Residual Current Device
· BYF-63 series RCD is a kind of circuit breaker with complete update of residual current detection, based on type A RCCB · It can only effectively protect AC and pulsing DC (A type), the possible compound residual current (F type), but also smoothing DC and high frequency residual current (1k Hz)
- Baisen / Customzied Logo
- Zhejiang, China
Details
PRODUCT FEATURES
In a circuit consisting of rectifier, inverter, etc, the leakage current caused in DC loop circuit can be effectively detected and protected
Application: industry, medical, EV charger, elevator, etc.
TECHNICAL PARAMETER
Type | Values | |||
Standard | IEC/EN 61008-1, IEC/EN 62643 | |||
Rated Voltage Ue | 1P: AC240V/415V; 2P, 3P, 4P: AC415V | |||
Rated Current In | 16A, 20A, 25A, 32A, 40A, 50A, 63A | |||
Poles | 1P+N, 3P+N | |||
Rated Residual Operated Current | 30mA, 100mA, 300mA | |||
Type of Residual Current | Type B (AC+A+smoothing DC+F+high frequency signal 1K Hz) | |||
Rated Limited Short Circuit Current Inc | 10kA/10,000A | |||
Rated Limited Short Circuit Current I△c | 10kA/10,000A | |||
Rated Making and Breaking Capacity Im | 1,000A | |||
Rated Residual Making and Breaking Capacity I△m | 1,000A | |||
Residual Insulation Voltage Ui | 500V | |||
Rated Impulse Withstand Voltage Uimp | 4kV | |||
Electrical Life | 1,000 Times | |||
Mechanical Life | 2,000 Times | |||
Connection Capacity | 16mm² | |||
Protection Level | IP20 |
DIMENSIONS